Shutter control
Works with bi-stable shutter.
You can find the device in /dev/shutterX (symlink to /dev/ttyUSBX).
Pinout
PB0 (pullup in) - hall (or reed switch) sensor input (active low) - opened shutter detector
PB11 (pullup in) - CCD or button input: open at low signal, close at high
PA3 (ADC in) - shutter voltage (approx 1/12 U)
PA5 (PP out) - TLE5205 IN2
PA6 (PP out) - TLE5205 IN1
PA7 (pullup in) - TLE5205 FB
PA10 (PP out) - USB pullup (active low)
PA11, PA12 - USB
PA13, PA14 - SWD
Commands
- '0' - shutter CLO
- '1' - shutter OPE
- '2' - shutter HIZ
- 'A' - get raw ADC values
- 'C' - close shutter / abort exposition
- 'E n' - expose for n milliseconds
- 'O' - open shutter
- 'R' - software reset
- 'S' - get shutter state; also hall and ccd inputs state (1 - active)
- 't' - get MCU temperature (/10degC)
- 'T' - get Tms
- 'v' - get Vdd (/100V)
- 'V' - get shutter voltage (/100V)
- 'W' - test watchdog
If you will enter wrong long message, will receive its echo back. Any wrong short command will show help list.
Shutter control
Commands '0', '1' and '2' should be used only for debugging purposes. To open/close shutter use only 'O', 'C' and 'E' commands.
When opening or closing shutter you will first receive an answer: OK if command could be done or ERR if there's insufficient voltage on capacitor or shutter is absent.
After opened the message shutter=opened will appear. After closing you will receive messages exptime=xxx (when xxx is approx. exp. time in milliseconds) and shutter=closed.
Command 'E' could return OK, ERR or ERRNUM/I32OVERFLOW in wrong number format (number could be decimal, 0x.. - hexadecimal, b.. - binary or 0.. - octal).
When exposition starts you will receive message OK and shutter=opened. After its end you'll got exptime=..., shutter=closed.
If shutter can't be closed, you will give a lots of "exp=cantclose" and different error messages until problem be solved. To stop this error messages give command 'O'.
Different commands
-
'A' will show raw values for all ADC channels: 0. - capacitor voltage, 1 - MCU temperature, 2 - MCU Vdd. You will give messages like
adcX=val. -
't' -
mcut=val, where val = T*10 degrC. -
'T' -
tms=val, val in ms. -
'v' -
vdd=val, val in V*100 -
'V' - "voltage=val", val in V*100
-
'S' - several answers:
shutter=:closed,opened,error,process,waitorexposing- shutter stateexptime=...(only when shutter is opened) - show time since openingregstate=:open,close,offorhiZ- TLE5205 outputs statefbstate=:0or1- TLE5205 FB out state (1 - error)hall=:0or1- 1 for opened shutter, 0 for closedccd=:0or1- 1 for active (closed contacts) state of "CCD" input