# awk '{printf "%s\t%s\t%s\t0\t# ", $1, $2, $3; $1=""; $2=""; $3=""; print $0}' orig > dictionary.dic
F00.00 61440 1 0 # Motor control (V/F)
F00.01 61441 0 0 # Start command source selection [0-keypad; 3,4 Modbus RTU]
F00.02 61442 0 0 # Communication type [0 - MODbus RTU]
F00.03 61443 5000 0 # Maximum frequency for VFD x100, Hz [from F00.04 to 500.00 Hz] (750 rpm)
F00.04 61444 5000 0 # Upper limit of operating frequency x100, Hz [F00.05 - F00.03] (610 rpm)
F00.05 61445 0 0 # Minimum frequency x100, Hz [from 0.00 to F00.04 Hz]
F00.06 61446 0 0 # Frequency source A from ... [0 - 9] [9 - Modbus RTU]
F00.07 61447 0 0 # Frequency source B from ... [0 - 9] (3)
F00.08 61448 0 0 # Frequency reference via channel B [0 - max frequency; 1 - frequency of channel A]
F00.09 61449 1000 0 # Maximum frequency via channel B x10 in % (100 rpm)
F00.10 61450 0 0 # Combined regulation mode [from 0 to 5] (0 => only A)
F00.11 61451 5000 0 # Combined mode frequency x100, Hz [from 0.00 to F00.03] (600 rpm)
F00.12 61452 100 0 # Acceleration time 1 x 10, sec. (30s)
F00.13 61453 100 0 # Deceleration time 1 x 10, sec. (30s)
F00.14 61454 0 0 # Rotation direction [from 0 - CW; 1 - CCW; 2 - prohibit CCW]
F00.15 61455 50 0 # Carrier modulation frequency 1 x 10 [from 2.0 to 10.0 kHz] (5 kHz)
F00.16 61456 0 0 # Speed tracking [from 0 to 2]
F00.17 61457 0 0 # Motor autotuning [0 - off; 1 - on with run; 2 - on without run;]
F00.18 61458 0 0 # Parameter reset [from 0 to 3; 0 - no reset]
F01.00 61696 0 0 # Start type: 0 - start from starting frequency; 1 - start after braking; 2 - start with speed search
F01.01 61697 50 0 # Starting frequency x100, [from 0 to 10 Hz] (7.5/101.48 = 0.074 rpm roller)
F01.02 61698 0 0 # Starting frequency hold time x10, [from 0.0 to 100.0 sec.] (test 1 s.)
F01.03 61699 0 0 # Braking current before start x10, % [from 00 to 150.0%]
F01.04 61700 0 0 # Braking time before start x10, sec. [from 0.0 to 100.0 sec]
F01.05 61701 0 0 # Acceleration/deceleration type [0 - linear; 1 - S curve;]
F01.06 61702 300 0 # Starting phase of S-curve x10, % [from 0.0 - 50.0% of accel/decel time]
F01.07 61703 300 0 # Final phase of S-curve x10, % [from 0.0 - 50.0% of accel/decel time]
F01.08 61704 0 0 # Stop method [0 - deceleration to stop; 1 - free coast]
F01.09 61705 0 0 # DC braking enable frequency x100, Hz
F01.10 61706 0 0 # DC braking waiting time x10, sec. [0 to 100]
F01.11 61707 0 0 # DC braking current during stop x10, % [0 to 100]
F01.12 61708 0 0 # DC braking time during stop x10, sec.
F01.13 61709 0 0 # Idle time between rotation direction changes x10, sec.
F01.14 61710 50 0 # Stop frequency x10, Hz
F01.15 61711 0 1 # Reserved
F01.16 61712 0 1 # Reserved
F01.17 61713 0 0 # Restart from terminals after power-on [0 - disabled 1 - enabled]
F01.18 61714 0 0 # Restart after voltage loss [0 - prohibit; 1 - restart]
F01.19 61715 10 0 # Restart delay x10, sec. [0.0 to 6000.0] (Only if F1.18 = 1)
F01.20 61716 0 1 # Reserved
F01.21 61717 0 0 # Action if output frequency is less than minimum; 0 - run at min frequency; 1 - stop; 2 - run at zero rotation speed.
F01.22 61718 5000 0 # Frequency reference in fire mode (x100), Hz.
F02.00 61952 0 0 # Load type [0 - type G; 1 - type P;]
F02.01 61953 0 0 # Motor type [0 - INDUCTION]
F02.02 61954 15 0 # Motor power x10, kW (5.5 kW)
F02.03 61955 380 0 # Motor voltage, V [0 - 1000.0] (380 V)
F02.04 61956 65 0 # Rated current x10, A (14.8 A)
F02.05 61957 5000 0 # Rated motor frequency x100, Hz
F02.06 61958 1450 0 # Rated motor speed according to nameplate, rpm
F02.07 61959 1414 0 # Stator resistance x100, Ohm (Value after autotuning!)
F02.08 61960 1264 0 # Rotor resistance x100, Ohm (Value after autotuning!)
F02.09 61961 67 0 # Leakage inductance x10, mH (Value after autotuning!)
F02.10 61962 956 0 # Motor inductance x10, mH (Value after autotuning!)
F02.11 61963 33 0 # No-load current x10, A (Value after autotuning!)
F02.12 61964 880 1 # Reserved
F02.13 61965 810 1 # Reserved
F02.14 61966 750 1 # Reserved
F02.15 61967 0 0 # Encoder type selection
F02.16 61968 1024 0 # Number of encoder pulses per revolution
F02.17 61969 0 0 # Encoder phase sequence ABZ
F02.18 61970 1 0 # Number of resolver pole pairs
F02.19 61971 1 1 # Reserved
F02.20 61972 3 1 # Reserved
F02.21 61973 3 1 # Reserved
F02.22 61974 10 1 # Reserved
F02.23 61975 10 1 # Reserved
F02.24 61976 1000 1 # Reserved
F02.25 61977 1 0 # Overload protection [0 - disabled; 1 - enabled;]
F02.26 61978 1000 0 # Overload protection coefficient x10, % [F02.26 x F02.04]
F03.00 62208 30 0 # Proportional coefficient of speed loop 1
F03.01 62209 50 0 # Integral time of speed loop 1 x1000, sec
F03.02 62210 500 0 # Low speed threshold x100, Hz
F03.03 62211 20 0 # Proportional coefficient of speed loop 2
F03.04 62212 100 0 # Integral time of speed loop 2 x1000, sec
F03.05 62213 1000 0 # High speed threshold 2 x100, Hz
F03.06 62214 15 0 # Feedback filtering coefficient x100, sec
F03.07 62215 0 0 # Proportional coefficient of current loop 1
F03.08 62216 0 0 # Integral time of current loop 1
F03.09 62217 0 0 # Proportional coefficient of current loop 2
F03.10 62218 0 0 # Integral time of current loop 2
F03.11 62219 0 0 # Torque limit channel selection
F03.12 62220 0 0 # Braking torque limit channel selection
F03.13 62221 1500 0 # Digital torque reference x10, %
F03.14 62222 1500 0 # Digital braking torque reference x10, %
F03.15 62223 100 0 # Torque limit coefficient
F03.16 62224 100 0 # Slip compensation coefficient, %
F04.00 62464 0 0 # V/F curve selection (linear characteristic)
F04.01 62465 0 0 # Torque boost x10, %
F04.02 62466 200 0 # Torque boost frequency x10, % ((300rpm/750rpm)*100)*10%
F04.03 62467 0 0 # V/F frequency 1 x100, Hz
F04.04 62468 0 0 # V/F voltage 1 x10, %
F04.05 62469 0 0 # V/F frequency 2 x100, Hz
F04.06 62470 0 0 # V/F voltage 2 x10, %
F04.07 62471 0 0 # V/F frequency 3 x100, Hz
F04.08 62472 0 0 # V/F voltage 3 x10, %
F04.09 62473 100 0 # Slip compensation x10, %
F04.10 62474 2 0 # Vibration control at low frequency
F04.11 62475 2 0 # Vibration control at high frequency
F04.12 62476 3000 0 # Vibration control threshold x100, Hz
F04.13 62477 0 0 # V/F curve selection Motor 2
F04.14 62478 0 0 # Torque boost x10, %
F04.15 62479 200 0 # Torque boost frequency x10, %
F04.16 62480 0 0 # V/F frequency 1 x100, Hz
F04.17 62481 0 0 # V/F voltage 1 x10, %
F04.18 62482 0 0 # V/F frequency 2 x100, Hz
F04.19 62483 0 0 # V/F voltage 2 x10, %
F04.20 62484 0 0 # V/F frequency 3 x100, Hz
F04.21 62485 0 0 # V/F voltage 3 x10, %
F04.22 62486 1000 0 # Slip compensation x10, %
F04.23 62487 2 0 # Vibration control at low frequency
F04.24 62488 2 0 # Vibration control at high frequency
F04.25 62489 3000 0 # Vibration control threshold x100, Hz
F04.26 62490 0 0 # Energy saving
F04.27 62491 0 0 # Voltage setting
F04.28 62492 1000 0 # Keypad reference x10, %
F04.29 62493 50 0 # Voltage increase time x10, sec.
F04.30 62494 50 0 # Voltage decrease time x10, sec.
F04.31 62495 1000 0 # Maximum output voltage x10, %
F04.32 62496 0 0 # Minimum output voltage x10, %
F04.33 62497 1 0 # AVR function selection
F04.34 62498 400 1 # Reserved
F05.00 62720 0 0 # DI5 terminal selection
F05.01 62721 1 0 # Terminal DI1
F05.02 62722 4 0 # Terminal DI2
F05.03 62723 7 0 # Terminal DI3
F05.04 62724 0 0 # Terminal DI4
F05.05 62725 0 0 # Terminal DI5 (discrete)
F05.06 62726 0 0 # Terminal DI6
F05.07 62727 0 0 # Terminal DI7 (optional)
F05.08 62728 0 0 # Terminal DI8 (optional)
F05.09 62729 0 0 # Input terminal polarity selection
F05.10 62730 10 0 # Input terminal debounce filter x1000, sec.
F05.11 62731 0 0 # Input terminal control setting
F05.12 62732 0 0 # Input terminal connection setting
F05.13 62733 0 0 # DI1 terminal switch-on delay x1000, sec.
F05.14 62734 0 0 # DI1 terminal switch-off delay x1000, sec.
F05.15 62735 0 0 # DI2 terminal switch-on delay x1000, sec.
F05.16 62736 0 0 # DI2 terminal switch-off delay x1000, sec.
F05.17 62737 0 0 # DI3 terminal switch-on delay x1000, sec.
F05.18 62738 0 0 # DI3 terminal switch-off delay x1000, sec.
F05.19 62739 0 0 # DI4 terminal switch-on delay x1000, sec.
F05.20 62740 0 0 # DI4 terminal switch-off delay x1000, sec.
F05.21 62741 0 0 # DI5 terminal switch-on delay x1000, sec.
F05.22 62742 0 0 # DI5 terminal switch-off delay x1000, sec.
F05.23 62743 0 0 # DI6 terminal switch-on delay x1000, sec.
F05.24 62744 0 0 # DI6 terminal switch-off delay x1000, sec.
F05.25 62745 0 0 # DI7 terminal switch-on delay x1000, sec.
F05.26 62746 0 0 # DI7 terminal switch-off delay x1000, sec.
F05.27 62747 0 0 # DI8 terminal switch-on delay x1000, sec.
F05.28 62748 0 0 # DI8 terminal switch-off delay x1000, sec.
F05.29 62749 0 1 # Reserved
F05.30 62750 0 0 # DI5 frequency lower limit x100, kHz
F05.31 62751 0 0 # DI5 frequency lower limit setting x10, %
F05.32 62752 5000 0 # DI5 frequency upper limit x100, kHz
F05.33 62753 1000 0 # DI5 frequency upper limit setting x10, %
F05.34 62754 100 0 # DI5 filtering time x1000, sec.
F05.35 62755 0 0 # Fire mode terminal operation mode
F06.00 62976 0 0 # HDO1 terminal configuration
F06.01 62977 0 0 # DO1 terminal function
F06.02 62978 0 0 # HDO1 terminal function
F06.03 62979 1 0 # Relay T1 function
F06.04 62980 5 0 # Relay T2 function
F06.05 62981 0 0 # Output terminal polarity selection
F06.06 62982 0 0 # DO1 terminal switch-on delay x1000, sec.
F06.07 62983 0 0 # DO1 terminal switch-off delay x1000, sec.
F06.08 62984 0 0 # HDO1 terminal switch-on delay x1000, sec.
F06.09 62985 0 0 # HDO1 terminal switch-off delay x1000, sec.
F06.10 62986 0 0 # Relay T1 switch-on delay x1000, sec.
F06.11 62987 0 0 # Relay T1 switch-off delay x1000, sec.
F06.12 62988 0 0 # Relay T2 switch-on delay x1000, sec.
F06.13 62989 0 0 # Relay T2 switch-off delay x1000, sec.
F06.14 62990 0 0 # AO1 output
F06.15 62991 0 0 # AO2 output
F06.16 62992 0 0 # HDO1 output (high-speed output)
F06.17 62993 0 0 # AO1 lower limit x10. %
F06.18 62994 200 0 # AO1 lower limit value x100, V
F06.19 62995 1000 0 # AO1 upper limit x10, %
F06.20 62996 1000 0 # AO1 upper limit value x100, V
F06.21 62997 0 0 # AO1 output filtering time x1000, sec.
F06.22 62998 0 0 # AO2 lower limit x10, %
F06.23 62999 0 0 # AO2 lower limit value x100, V
F06.24 63000 1000 0 # AO2 upper limit x10, %
F06.25 63001 1000 0 # AO2 upper limit value x100, V
F06.26 63002 0 0 # AO2 output filtering time x1000, sec.
F06.27 63003 0 0 # HDO1 lower limit x10, %
F06.28 63004 0 0 # HDO1 lower limit value x100, kHz
F06.29 63005 1000 0 # HDO1 upper limit x10, %
F06.30 63006 5000 0 # HDO1 upper limit value x100, kHz
F06.31 63007 0 0 # HDO1 output filtering time x1000, sec.
F06.32 63008 1 0 # Brake control function
F06.33 63009 500 0 # Brake release frequency during lifting x100, Hz
F06.34 63010 20 0 # Brake release current during lifting, % of rated current
F06.35 63011 600 0 # Brake release delay frequency during lifting x100, Hz
F06.36 63012 2 0 # Brake release delay time during lifting x10, sec.
F06.37 63013 500 0 # Brake engage frequency during lifting x100, Hz
F06.38 63014 450 0 # Brake engage delay frequency during lifting x100, Hz
F06.39 63015 2 0 # Brake engage delay time during lifting x10, sec.
F06.40 63016 500 0 # Brake release frequency during lowering x100, Hz
F06.41 63017 20 0 # Brake release current during lowering, % of rated current
F06.42 63018 600 0 # Brake release delay frequency during lowering x100, Hz
F06.43 63019 2 0 # Brake release delay time during lowering x100, sec.
F06.44 63020 500 0 # Brake engage frequency during lowering x100, Hz
F06.45 63021 450 0 # Brake engage delay frequency during lowering x100, sec.
F06.46 63022 2 0 # Brake engage delay time during lowering x10, sec.
F06.47 63023 1000 0 # Torque limit with brake engaged x10, %
F07.00 63232 0 0 # User password
F07.01 63233 0 0 # S button function selection
F07.02 63234 255 0 # Status parameters 1
F07.03 63235 255 0 # Status parameters 2
F07.04 63236 255 0 # Status parameters at stop
F07.05 63237 100 0 # Frequency coefficient x100
F07.06 63238 1000 0 # Rotation speed x10, %
F07.07 63239 10 0 # Linear speed coefficient x10, %
F07.08 63240 36 1 # Rectifier temperature, C
F07.09 63241 36 1 # Inverter temperature, C
F07.10 63242 60770 1 # Software version
F07.11 63243 0 1 # Operating time, hour.
F07.12 63244 0 1 # AI1 alarm lower limit, V
F07.13 63245 680 1 # AI1 alarm upper limit, V
F07.14 63246 0 1 # Selection of channel for upper limit of PID regulator output
F07.15 63247 15 1 # VFD rated power x10, kW
F07.16 63248 380 1 # Rated voltage, V
F07.17 63249 75 1 # Rated current x10, A
F07.18 63250 0 1 # Current fault
F07.19 63251 0 1 # Fault at previous trip
F07.20 63252 0 1 # Fault at 2nd trip
F07.21 63253 0 1 # Fault at 3rd trip
F07.22 63254 0 1 # Fault at 4th trip
F07.23 63255 0 1 # Fault at 5th trip
F07.24 63256 0 1 # Frequency at current fault x100, Hz
F07.25 63257 0 1 # Reference frequency at current fault x100, Hz
F07.26 63258 0 1 # Output voltage at current fault, V
F07.27 63259 0 1 # Output current at current fault x10, V
F07.28 63260 0 1 # DC link voltage at current fault x10, V
F07.29 63261 0 1 # Maximum VFD temperature at current fault x10, C
F07.30 63262 0 1 # Input terminal state at current fault
F07.31 63263 0 1 # Output terminal state at current fault
F07.32 63264 0 1 # Output frequency at previous fault x100, Hz
F07.33 63265 0 1 # Reference frequency at previous fault x100, Hz
F07.34 63266 0 1 # Output voltage at previous fault, V
F07.35 63267 0 1 # Output current at previous fault x10, A
F07.36 63268 0 1 # DC link voltage at previous fault x10, V
F07.37 63269 0 1 # Maximum VFD temperature at previous fault x10, C
F07.38 63270 0 1 # Input terminal state at previous fault
F07.39 63271 0 1 # Output terminal state at previous fault
F07.40 63272 0 1 # Frequency at 2nd fault x100, Hz
F07.41 63273 0 1 # Reference frequency at 2nd fault x100, Hz
F07.42 63274 0 1 # Output voltage at 2nd fault, V
F07.43 63275 0 1 # Output current at 2nd fault x10, A
F07.44 63276 0 1 # DC link voltage at 2nd fault, V
F07.45 63277 0 1 # Maximum VFD temperature at 2nd fault x10, C
F07.46 63278 0 1 # Input terminal state at 2nd fault
F07.47 63279 0 1 # Output terminal state at 2nd fault
F08.00 63488 100 0 # Acceleration time 2 x10, sec.
F08.01 63489 100 0 # Deceleration time 2 x10, sec.
F08.02 63490 100 0 # Acceleration time 3 x10, sec.
F08.03 63491 100 0 # Deceleration time 3 x10, sec.
F08.04 63492 100 0 # Acceleration time 4 x10, sec.
F08.05 63493 100 0 # Deceleration time 4 x10, sec.
F08.06 63494 500 0 # Jog frequency x100, Hz
F08.07 63495 100 0 # Jog mode acceleration time x10, sec.
F08.08 63496 100 0 # Jog mode deceleration time x10, sec.
F08.09 63497 0 0 # Number of fault resets
F08.10 63498 10 0 # Automatic reset delay time x10, sec.
F08.11 63499 0 0 # Frequency decrease control x100, Hz
F08.12 63500 0 0 # Motor switching
F08.13 63501 5000 0 # FDT1 frequency reach level x100, Hz
F08.14 63502 50 0 # FDT1 hold x10, %
F08.15 63503 5000 0 # FDT1 frequency reach level x100, Hz
F08.16 63504 50 0 # FDT2 hold x10, %
F08.17 63505 0 0 # Frequency detection width x100, Hz
F08.18 63506 1 0 # Braking chopper
F08.19 63507 3800 0 # Actuation voltage level x10, V
F08.20 63508 0 0 # PWM compensation
F08.21 63509 0 0 # Keypad button function
F08.22 63510 10 0 # Button 'UP'/'DOWN' delay time x10, sec.
F08.23 63511 0 0 # Button 'UP'/'DOWN' reference
F08.24 63512 50 0 # Button 'UP' delay time x100, sec.
F08.25 63513 50 0 # Button 'DOWN' delay time x100, sec.
F08.26 63514 0 0 # Frequency at power loss
F08.27 63515 50 0 # Magnetic flux braking x100, sec.
F08.28 63516 1 0 # Auxiliary monitoring
F08.29 63517 0 0 # Parameter copy (panel only)
F08.30 63518 0 0 # Additional input/output board
F08.31 63519 0 0 # Braking at power loss
F08.32 63520 0 0 # Braking time at power loss x10, sec.
F08.33 63521 2000 0 # Actuation voltage, V
F08.34 63522 5000 0 # Arbitrary frequency 1 x100, Hz
F08.35 63523 0 0 # Arbitrary frequency 1 detection width
F08.36 63524 5000 0 # Arbitrary frequency 2 x100, Hz
F08.37 63525 0 0 # Arbitrary frequency 2 detection width
F08.38 63526 0 0 # Jog mode during operation
F09.00 63744 0 0 # PID setpoint source
F09.01 63745 500 0 # PID setpoint x10, %
F09.02 63746 0 0 # PID feedback
F09.03 63747 0 0 # Feedback type
F09.04 63748 200 0 # Proportional component (Kp) x10
F09.05 63749 20 0 # Integral component (Ti) x10
F09.06 63750 0 0 # Differential component (Td) x100
F09.07 63751 10 0 # Sampling cycle (T) x100, sec.
F09.08 63752 2 0 # PID deviation limit x10, %
F09.09 63753 1000 0 # PID upper limit x10, %
F09.10 63754 0 0 # PID lower limit x10, %
F09.11 63755 0 0 # Feedback signal value activating signal loss fault x10, %
F09.12 63756 10 0 # Signal loss fault switch-on delay x10, sec.
F09.13 63757 0 1 # Reserved
F09.14 63758 50 0 # Proportional component 2 (Kp2) x100
F09.15 63759 20 0 # Integral component 2 (Ti2) x100
F09.16 63760 0 0 # Differential component 2 (Td2) x100
F09.17 63761 0 0 # PID parameter switching
F09.18 63762 200 0 # PID deviation threshold x10, %
F09.19 63763 600 0 # Sleep frequency x100, %
F09.20 63764 0 0 # Sleep delay x10, sec.
F09.21 63765 0 0 # Wake-up coefficient x10, %
F09.22 63766 5 0 # Wake-up delay x10, sec
F09.23 63767 0 0 # Preset PID value x10, %
F09.24 63768 0 0 # Preset PID value hold time x10, sec.
F0A.00 64000 0 0 # Oscillation frequency x10, %
F0A.01 64001 0 0 # Jog frequency amplitude x10, sec.
F0A.02 64002 0 0 # Oscillation frequency increase time x10, sec.
F0A.03 64003 0 0 # Oscillation frequency decrease time x10, sec.
F0A.04 64004 0 0 # Length setting, m
F0A.05 64005 0 1 # Set length, m
F0A.06 64006 1 0 # Number of pulses per revolution
F0A.07 64007 1000 0 # Shaft circumference x100, m
F0A.08 64008 1000 0 # Multiplier x1000
F0A.09 64009 1000 0 # Correction coefficient x1000
F0A.10 64010 0 0 # Counter set value
F0A.11 64011 0 0 # Counter determined value
F0A.12 64012 0 0 # Operating time, min.
F0A.13 64013 0 0 # Stop method
F0A.14 64014 0 1 # Reserved
F0B.00 64256 0 0 # Simple PLC mode
F0B.01 64257 0 0 # PLC operation mode at power failure
F0B.02 64258 0 0 # Multi-speed mode 0 x10, %
F0B.03 64259 0 0 # Operation time in mode 0 x10, sec.
F0B.04 64260 0 0 # Multi-speed mode 1 x10, %
F0B.05 64261 0 0 # Operation time in mode 1 x10, sec.
F0B.06 64262 0 0 # Multi-speed mode 2 x10, %
F0B.07 64263 0 0 # Operation time in mode 2 x10, sec.
F0B.08 64264 0 0 # Multi-speed mode 3 x10, %
F0B.09 64265 0 0 # Operation time in mode 3 x10, sec.
F0B.10 64266 0 0 # Multi-speed mode 4 x10, %
F0B.11 64267 0 0 # Operation time in mode 4 x10, sec.
F0B.12 64268 0 0 # Multi-speed mode 5 x10, %
F0B.13 64269 0 0 # Operation time in mode 5 x10, sec.
F0B.14 64270 0 0 # Multi-speed mode 6 x10, %
F0B.15 64271 0 0 # Operation time in mode 6 x10, sec.
F0B.16 64272 0 0 # Multi-speed mode 7 x10, %
F0B.17 64273 0 0 # Operation time in mode 7 x10, sec.
F0B.18 64274 0 0 # Multi-speed mode 8 x10, %
F0B.19 64275 0 0 # Operation time in mode 8 x10, sec.
F0B.20 64276 0 0 # Multi-speed mode 9 x10, %
F0B.21 64277 0 0 # Operation time in mode 9 x10, sec.
F0B.22 64278 0 0 # Multi-speed mode 10 x10, %
F0B.23 64279 0 0 # Operation time in mode 10 x10, sec.
F0B.24 64280 0 0 # Multi-speed mode 11 x10, %
F0B.25 64281 0 0 # Operation time in mode 11 x10, sec.
F0B.26 64282 0 0 # Multi-speed mode 12 x10, %
F0B.27 64283 0 0 # Operation time in mode 12 x10, sec.
F0B.28 64284 0 0 # Multi-speed mode 13 x10, %
F0B.29 64285 0 0 # Operation time in mode 13 x10, sec.
F0B.30 64286 0 0 # Multi-speed mode 14 x10, %
F0B.31 64287 0 0 # Operation time in mode 14 x10, sec.
F0B.32 64288 0 0 # Multi-speed mode 15 x10, %
F0B.33 64289 0 0 # Operation time in mode 15 x10, sec.
F0B.34 64290 0 0 # PLC acceleration and deceleration values (0 - 7)
F0B.35 64291 0 0 # PLC acceleration and deceleration values (8 - 15)
F0B.36 64292 0 0 # PLC restart
F0B.37 64293 0 0 # PLC restart mode
F0C.00 64512 11 0 # Phase loss protection
F0C.01 64513 0 0 # Frequency decrease at power failure x100, Hz/sec.
F0C.02 64514 1000 0 # Frequency decrease rate at power failure x100, Hz/sec.
F0C.03 64515 0 0 # Overvoltage during stall
F0C.04 64516 140 0 # Overvoltage level during stall, %
F0C.05 64517 1 0 # Current limit
F0C.06 64518 1660 0 # Automatic current limit x10, %
F0C.07 64519 1000 0 # Frequency decrease step at current limit x100, Hz/sec.
F0C.08 64520 0 0 # Overload protection
F0C.09 64521 166 0 # Overload detection pre-alarm, %
F0C.10 64522 0 0 # Overload detection time x100, sec.
F0C.11 64523 0 0 # Low load pre-alarm, %
F0C.12 64524 30 0 # Low load detection pre-alarm, %
F0C.13 64525 10 0 # Low load detection time x10, sec.
F0C.14 64526 0 0 # Alarm modes on low load detection
F0C.15 64527 0 0 # Carrier frequency adjustment selection
F0C.16 64528 1 0 # PWM mode
F0C.17 64529 1 0 # Low-pass filter
F0C.18 64530 1 1 # Reserved
F0D.00 64768 1 0 # Second motor control method
F0D.01 64769 1 0 # Load type
F0D.02 64770 1 0 # Second motor type
F0D.03 64771 15 0 # Rated motor power 2 x10, kW
F0D.04 64772 380 0 # Rated motor voltage 2, V
F0D.05 64773 65 0 # Rated motor current 2 x10, A
F0D.06 64774 5000 0 # Rated motor frequency 2 x100, Hz
F0D.07 64775 1450 0 # Rated motor speed 2 x10, rpm
F0D.08 64776 1414 0 # Stator resistance motor 2 x1000, Ohm
F0D.09 64777 1264 0 # Rotor resistance motor 2 x1000, Ohm
F0D.10 64778 67 0 # Leakage inductance motor 2 x10
F0D.11 64779 956 0 # Motor inductance 2 x10
F0D.12 64780 33 0 # No-load current motor 2 x10, A
F0D.13 64781 1 1 # Reserved
F0D.14 64782 1 1 # Reserved
F0D.15 64783 1 1 # Reserved
F0D.16 64784 1 1 # Reserved
F0D.17 64785 1 1 # Reserved
F0D.18 64786 1 1 # Reserved
F0D.19 64787 1 1 # Reserved
F0D.20 64788 1 1 # Reserved
F0D.21 64789 1 1 # Reserved
F0D.22 64790 1 1 # Reserved
F0D.23 64791 1 1 # Reserved
F0D.24 64792 1 1 # Reserved
F0D.25 64793 1 1 # Reserved
F0D.26 64794 1 0 # Overload protection for motor 2
F0D.27 64795 1000 0 # Motor 2 overload detection x10, %
F0E.00 65024 1 0 # Network address
F0E.01 65025 4 0 # Baud rate
F0E.02 65026 4 0 # Communication type
F0E.03 65027 5 0 # Response delay
F0E.04 65028 0 0 # Communication loss detection time x10, sec
F0E.05 65029 0 0 # Data transmission fault
F0E.06 65030 0 0 # Reserved
F0E.07 65031 200 0 # Reserved
F0E.08 65032 0 0 # Reserved
A00.00 40960 0 0 # Speed/torque control
A00.01 40961 0 0 # Reference channel when torque control selected
A00.02 40962 1500 0 # Digital torque reference x10, %
A00.03 40963 0 0 # Acceleration time in torque control x10, sec.
A00.04 40964 0 0 # Deceleration time in torque control x10, sec.
A00.05 40965 0 0 # Selection of forward rotation frequency limit channel in torque control
A00.06 40966 5000 0 # Digital forward rotation frequency limit x100, Hz
A00.07 40967 0 0 # Selection of reverse rotation frequency limit channel in torque control
A00.08 40968 5000 0 # Digital reverse rotation frequency limit x100, Hz
A00.09 40969 0 0 # Zero speed torque compensation coefficient x10, %
A00.10 40970 300 0 # Zero speed detection level x100, Hz
A00.11 40971 0 0 # Sliding friction compensation coefficient x10, %
A01.00 41216 0 0 # AI1 input lower limit x100, V, mA
A01.01 41217 0 0 # AI1 input lower limit correspondence x10, %
A01.02 41218 1000 0 # AI1 input upper limit x100, V, mA
A01.03 41219 1000 0 # AI1 input upper limit correspondence x10, %
A01.04 41220 100 0 # AI1 input filter x1000, sec.
A01.05 41221 0 0 # AI2 input lower limit x100, V, mA
A01.06 41222 0 0 # AI2 input lower limit correspondence x10, %
A01.07 41223 1000 0 # AI2 input upper limit x100, V, mA
A01.08 41224 1000 0 # AI2 input upper limit correspondence x10, %
A01.09 41225 0 0 # AI2 input average value x100, V
A01.10 41226 0 0 # AI2 input average value correspondence x10, %
A01.11 41227 100 0 # AI2 input filter x1000, sec.
A01.12 41228 0 0 # AI3 input lower limit x100, V
A01.13 41229 0 0 # AI3 input lower limit correspondence x10, %
A01.14 41230 1000 0 # AI3 input upper limit x100, V
A01.15 41231 1000 0 # AI3 input upper limit correspondence x10, %
A01.16 41232 500 0 # AI3 input average value x100, V
A01.17 41233 500 0 # AI3 input average value correspondence x10, %
A01.18 41234 100 0 # AI3 input filter x1000, sec
A01.19 41235 50 0 # Contact debounce filter x1000, sec.
A02.00 41472 0 1 # Set frequency x100, Hz
A02.01 41473 0 1 # Output frequency x100, Hz
A02.02 41474 0 1 # Acceleration reference frequency x100, Hz
A02.03 41475 0 1 # Output voltage, V
A02.04 41476 0 1 # Output current x10, A
A02.05 41477 0 1 # Motor speed, rpm
A02.06 41478 0 1 # Reserved
A02.07 41479 0 1 # Reserved
A02.08 41480 0 1 # Output power x10, %
A02.09 41481 0 1 # Output torque x10, %
A02.10 41482 0 1 # Motor frequency estimate x100, Hz
A02.11 41483 0 1 # DC link voltage, V
A02.12 41484 0 1 # Discrete input state
A02.13 41485 0 1 # Discrete output state
A02.14 41486 0 1 # Digital frequency reference x100, Hz
A02.15 41487 0 1 # Reserved
A02.16 41488 0 1 # Linear speed
A02.17 41489 0 1 # Pulse length
A02.18 41490 0 1 # Counter value
A02.19 41491 0 1 # AI1 input voltage x100, V
A02.20 41492 0 1 # AI2 input voltage x100, V
A02.21 41493 0 1 # AI3 input voltage x100, V
A02.22 41494 0 1 # HDI1 input frequency x100, kHz
A02.23 41495 0 1 # PID setpoint x10, %
A02.24 41496 0 1 # PID feedback x10, %
A02.25 41497 0 1 # PID output signal x100, %
A02.26 41498 0 1 # Power factor x10, %
A02.27 41499 0 1 # Operating time, min.
A02.28 41500 0 1 # PLC operation step
A02.29 41501 0 1 # ASR regulator output signal x10, %
A02.30 41502 0 1 # A01 output voltage x100, V
A02.31 41503 0 1 # A02 output voltage x100, V
A02.32 41504 0 1 # VFD current x10, A
A02.33 41505 0 1 # Torque x10
A02.34 41506 0 1 # Motor overload counter
A02.35 41507 0 1 # Reserved
A02.36 41508 1 1 # Current motor selection
A03.00 41728 0 0 # Telegram type
A03.01 41729 1 0 # Device address
A03.02 41730 0 0 # Parameter in telegram PZD3 (write to VFD - DateOutput, %QW)
A03.03 41731 0 0 # Parameter in telegram PZD4 (write to VFD - DateOutput, %QW)
A03.04 41732 0 0 # Parameter in telegram PZD5 (write to VFD - DateOutput, %QW)
A03.05 41733 0 0 # Parameter in telegram PZD6 (write to VFD - DateOutput, %QW)
A03.06 41734 0 0 # Parameter in telegram PZD7 (write to VFD - DateOutput, %QW)
A03.07 41735 0 0 # Parameter in telegram PZD8 (write to VFD - DateOutput, %QW)
A03.08 41736 0 0 # Parameter in telegram PZD9 (write to VFD - DateOutput, %QW)
A03.09 41737 0 0 # Parameter in telegram PZD10 (write to VFD - DateOutput, %QW)
A03.10 41738 0 0 # Parameter in telegram PZD11 (write to VFD - DateOutput, %QW)
A03.11 41739 0 0 # Parameter in telegram PZD12 (write to VFD - DateOutput, %QW)
A03.12 41740 0 0 # Reserved
A03.13 41741 0 0 # Reserved
A03.14 41742 0 0 # Parameter in telegram PZD3 (read from VFD - DateInput, %IW)
A03.15 41743 0 0 # Parameter in telegram PZD4 (read from VFD - DateInput, %IW)
A03.16 41744 0 0 # Parameter in telegram PZD5 (read from VFD - DateInput, %IW)
A03.17 41745 0 0 # Parameter in telegram PZD6 (read from VFD - DateInput, %IW)
A03.18 41746 0 0 # Parameter in telegram PZD7 (read from VFD - DateInput, %IW)
A03.19 41747 0 0 # Parameter in telegram PZD8 (read from VFD - DateInput, %IW)
A03.20 41748 0 0 # Parameter in telegram PZD9 (read from VFD - DateInput, %IW)
A03.21 41749 0 0 # Parameter in telegram PZD10 (read from VFD - DateInput, %IW)
A03.22 41750 0 0 # Parameter in telegram PZD11 (read from VFD - DateInput, %IW)
A03.23 41751 0 0 # Parameter in telegram PZD12 (read from VFD - DateInput, %IW)
A03.24 41752 0 0 # Reserved
A03.25 41753 0 0 # Reserved